Sieyuan Oil Immersed Current Transformers (CTs)

Precision-engineered current transformers built to IEC/IEEE standards deliver exceptional measurement accuracy, stable performance, and robust protection against system faults and surges.

 

LVB series current transformers are of oil impregnated paper insulation and inverted structure to meet the IEC/IEEE standard. The series connected transformer in the line has the functions of electric energy measure-ment, metering, relay protection and transient protection.

  • The primary winding is of through type conductive rod structure, with good dynamic and thermal stability. The maximum thermal stability current is 63kA/3s (when the primary winding is in series).
  • The primary winding passes through the center of the secondary winding without the influence of magnetic flux leakage, and the measurement accuracy reaches 0.2S and 0.1.
  • The secondary winding is poured into the aluminum shield housing with organic materials, and the measuring and protection lines at the secondary side will not be subject to electrical attack due to insulation breakdown.
  • The optimized capacitor screen bushing is wound by a high-performance computer controlled full-automatic wrapping machine with a whole sheet of imported wide width cable paper. The process dispersion is small, and the insulation performance is excellent. The partial discharge test is conducted under the power frequency test voltage.
  • The fully automatic vacuum drying treatment system imported from Germany LEYBOLD is adopted. After the overall assembly of the product, the new process of variable pressure vacuum drying treatment and oil injection is carried out. The fully imported insulating materials ensure that the overall dielectric loss factor tand of the product is less than 0.3%.
  • The head insulation of the product is wrapped with an automatic binding machine, and the insulation wrapping of the product is uniform, tight and consistent.
  • The secondary outlet box is cast with aluminum alloy as a whole, with a dust-proof, waterproof and breathable sealing structure.
  • The connection between product parts adopts argon arc welding, and the whole assembly is filled with high-pressure nitrogen for leak detection, which fundamentally solves the problem of oil leakage of oil immersed products.
  • The shell, base and junction box are all made of aluminum alloy. The expander and nameplate are made of stainless steel. All exposed parts will never rust.
  • The product is maintenance free.

Technical Parameter

Type

Highest voltage (kV)

Rated frequency (Hz)

Power-frequency voltage (kV)

Lightning impulse voltage (BIL)(kV)

Rated primary current(A)

Class

LVB-31.5

31.5

50/60

95

200

IEC:

Min current: 0.5A;

Max current: 8000A:

IEEE:

MR5000/MR4000/
MR3000/MR2000/
MR1200/MR600

IEC:

0.2/0.5/0.2S/0.5S/5P/
10P/TPS/TPX/TPY

IEEE:

0.3/0.6/1.2/C200/C40
0/C800

LVB-40.5

40.5

50/60

95

200

LVB-72.5

72.5

50/60

160

350

LVB-110

123

50/60

230

550

LVB-126

126

50/60

230

550

LVB-145

145

50/60

275

650

LVB-170

170

50/60

325

750

LVB-245

252

50/60

460

1050

LVB-300

300

50/60

460

1050

LVB-363

363

50/60

510

1175

LVB-420

420

50/60

630

1425

LVB-550

550

50/60

740

1675

                                                                          

Technical Parameter

Type

Thermal current (kA)

Dynamic current (kA)

Oil weight (kg)

Total weight (kg)

Dimensions

A(mm)

T(mm)

H(mm)

LVB-31.5

31.5kA/3S

80

34

140

300

984±25

1464±30

LVB-40.5

40kA/3S

100

78

315

475

1075±15

1615±25

LVB-72.5

80

350

475

1290±25

1815±25

LVB-110

50kA/3S

125

80

400

475

1790±15

2310±25

LVB-126

80

400

475

1790±15

2310±25

LVB-145

80

400

475

2198±15

2730±25

LVB-170

100

500

475

2198±15

2730±25

LVB-245

63kA/3S

160

180

800

550

2955±15

3650±25

LVB-300

222

935

550

3585±25

4285±30

LVB-363

330

1200

600

4535±25

5100±20

LVB-420

440

1400

600

4750±25

5650±30

LVB-550

550

2600

650

5920±15

7015±20

 

Remark: Approximate dimensions and weights for special requirements, please consult us.

Options

DIN-style switchgear (EFEN or third-party brand)

Street lighting and other auxiliary supplies

MDI’s / metering / monitoring

Other switchgear or control gear

Other literature available on request

Reports, drawings, technical data sheets, installation instructions, O&M guidelines