Insulect Gas Insulated Load Break Switch

Gas insulated load break switch 12kV, 24kV, 36kV.

 

The fully enclosed, pole-mounted SF6 load break switch, from our brand partner Insulect, is used extensively throughout distribution networks and are designed to be maintenance-free with long service life.

12, 24, 36kV voltage rating: The switch can be supplied in 12, 24 & 36kV voltage ratings and up to 630A breaking current.

Safer, more reliable switching: Fully enclosed, SF6 insulation and interruption provides greater reliability.

Local or remote operation: Manually operated LBS can be fitted with a remotely controlled actuator.

Insulators and leads: Choose from porcelain or polymer bushings, with factory fitted cable leads or bare terminal palms.

Features include:

  • Stainless steel enclosure
  • Easy handling and light weight
  • Open/close indicator
  • Maintenance free
  • Low gas lockout feature
  • High dielectric strength
  • Superior endurance to adverse environments Mechanical latch holding in close position
  • Pole mounting provisions
  • Pressure relief vent.

Parameter

Unit

12kV

24kV

36kV

Rated Voltage

kV

12

12

24

24

36

36

Rated Frequency

Hz

50/60

50/60

50/60

50/60

50/60

50/60

Rated Normal Current

A

400

630

400

630

400

630

Rated Symmetrical Interrupting Current

A

400

630

400

630

400

630

Rated Short-Time Withstand Current, 1 sec

kA (rms)

16

16

16

16

16

16

Rated Short-Circuit Making Current

kA (peak)

41.6

41.6

41.6

41.6

41.6

41.6

Rated Power Frequency Withstand Voltage, 1 min

kA (rms)

70

70

70

70

70, 80

70, 80

Rated Impulse Withstand Voltage

kA (peak)

165

165

165

165

170, 195

170, 195

Number of Operations: Mechanical, Electrical (rated normal current)

times

5000

5000

5000

5000

5000

5000

Minimum Creepage Distance of Bushing or Supporting Insulator, from live part to ground

mm

min 600

min 600

min 600

min 600

min 900

min 900

Other literature available on request