AegisEcoTec Ring Main Unit

A breath of fresh air for electrical distribution.

The new AegisEcoTec Ring Main Unit (RMU) uses synthetic air, not SF6 as the insulating medium, bringing environmental advantages for medium voltage (MV) switchgear.

 

The AegisEcoTec non-SF6 Ring Main Unit (RMU) range is designed to be smaller and more efficient, while maintaining compatibility with standard installation requirements. As a result, the EcoTec range provides the same set of solutions for substations as conventional equivalents, but in a more compact and optimised package.

Across the Aegis range, operator safety is paramount with integral interlocking at the forefront of its innovative mechanism design. With a clear, unambiguous mimic and 100% padlockable human-machine interface (HMI), this solution is straightforward and secure.

To ensure the high industrial and operational reliability NZ’s networks need, AegisEcoTec 12kV non-SF6 RMUs use the same core mechanism design as the hugely successful Aegis RMU range which is installed worldwide.

AegisEcoTec non-SF6 RMU uses synthetic air bringing environmental advantages for medium voltage (MV) switchgear. For load break switching, a new architecture is necessary.

AegisEcoTec non-SF6 RMU uses a small load break vacuum interrupter (VI) shunted across the main current-carrying contacts. This shunt VI breaks the load current, ensuring there is no arcing of the main current-carrying contacts.

AegisEcoTec

Width (mm)

Depth (mm)

Height (mm)

2-way

720

704

1669

3-way

1060

704

1669

4-way

1400

704

1669

Parameters

Specifications

12kV

Rated voltage

kV

12

Rated frequency

Hz

50

Rated impulse withstand voltage

kV

95

Rated power frequency withstand voltage

kV

38

Short time withstand current

kA

20

Rated duration of short circuit

Seconds

3

Short peak withstand current

kA

52.5

Internal arc classification

 

AF/AFL/AFLR

Internal arc rating:       Tank

kA 1 second

20

                                            Cable Box

kA 1 second

13.5 / 20

Ingress protection:     Outdoor

IP

54

                                            Indoor

IP

41

Temperature range

°C

-25 to +40

Maximum relative humidity

%

95

Circuit Breaker Functions

Parameters

Specifications

12kV

Rated normal current:     T function

A

250

                                                V function

A

630

Mechanical endurance

Class

M1

Electrical endurance

Class

E2

 

Load Break Functions

Parameters

Specifications

12kV

Rated normal current

A

630

Mechanical endurance

Class

M1

Electrical endurance

Class

E3