Pfisterer CONNEX Separable Connector

CONNEX Separable Connector, Size 4, up to 72.5 kV

  • Pluggable separable connector for all XLPE cables
  • Available as factory-tested and preassembled field installation cable

 

The dry pluggable CONNEX connection system connects the transformer, MV and HV GIS without timeconsuming SF6 gas work.

CONNEX connection joints in cast resin technology up to 170 kV enable pluggable connections that can be separated quickly if necessary. The longitudinal water barrier prevents water penetration as a result of cable faults.

The solid-insulated CONNEX connections are maintenance-free and the only ones on the market with. DNV – GL certification.

  • The separable connector is installed without any gas- and oil work at the transformer or GIS
  • Considerably reduced installation time and safe installation
  • Horizontal, vertical and angled versions for connection to GIS and transformers
  • Rapid separation and change of cable and equipment possible
  • Touchproof, submersible, and maintenance-free
  • Routine-tested from factory

*) depending on conductor cross section and conductor material

Article no.

Unit

849 999 999 xxxxx

Max. system voltage

Um (kV)

72,5

Size

 

4

Type designation

 

dry-type termination

Applicable standards

 

IEC 60840:2011

Working place

 

outdoor and indoor offshore on request

Nominal voltage

Un (kV)

60 – 69

Conductor residual voltage

U0 (kV)

36

Rated power frequency withstand voltage

1 min (kV)

140

Rated lightning impulse withstand voltage BIL

(kV)

325

Heating cycles

(kV)

72

Partial discharge test < 5pc at

(kV)

54

Rated power frequency withstand voltage – 30 min

(kV)

90

Partial discharge test < 2pC at

(kV)

54

Nominal current*)

IN (A)

2500

Rated short-time withstand current

(kA)

50

Rated impulse current CALCULATED

(kA)

160

Conductor material

 

copper or aluminium

Diameter of conductor

Ø (mm)

9.3 – 55.9

Conductor cross section area

(mm2)

95 – 2000

Diameter of insulating

(mm)

33 – 78.5

Connection method

 

Compression connection

Length outside socket

(mm)

580